What’s right for you? PLC or Safety PLC?

Written By: Vijay Kapila

Controls CabinetDo you need a PLC (programmable logic controller) or a safety PLC? The answer depends on the safety requirement of the system or equipment in question. There are PLCs and there are safety PLCs which have safety built into them. So what’s the difference, and what should you be using for your automated system when there is a stringent safety requirement?

Each automated system or piece of equipment has an individual safety requirement based on the category of the safety circuit, and there are four different categories for safety circuits:

  1. Category 1: Single channel to safety relay, the lowest category of safety circuits.
  2. Category 2: Two channels for a safety circuit; the first channel is hardwired to an e-stop chain, the second channel can be another hardwire or PLC monitoring of auxiliary contacts on safety switches.
  3. Category 3: Two hardwired channels for a safety circuit; drives with a “safe off” feature generally fall under this category.
  4. Category 4: Two hardwired channels for a safety circuit with a self-monitoring safety relay. This is the most stringent of categories and the one most of the automotive industry follows.

PLCs can be programmed to do just about anything these days, from simple discrete logic, to a complex hybrid control. But why not take it a step further and use the PLC to detect and respond to potentially dangerous failures? This keeps safety top of mind and helps to get the system safety certified.

It can definitely be DONE, and it can be accomplished in two ways:

1. Using a Normal PLC for a Safety Circuit

Programmable Logic Controller from Allen Bradley

Here is an example of a typical PLC. This model is manufactured by Allen Bradley.

A controls system can be designed with a normal PLC and can be programmed however we want. A system can also be designed and programmed with any level of complexity with a PLC such that it can detect any kind of failure and put the equipment in a stopped, safe and controlled manner. To achieve a certain safety category with a normal PLC, all the equipment needs to be hard-wired as explained in the above categories for that equipment’s specific safety-circuit category.

Pros of using a normal PLC:

  • Simple to wire and troubleshoot
  • Cost effective for simple systems

Cons of using a normal PLC:

  • Many different relay types
  • Problems increase with an increase in relays and can quickly get complicated
  • Poor diagnostics and poor status indicators
  • Very difficult to do multiple e-stop zones

2. Using a Safety PLC

Safety PLC for equipment automation

Here is an example of a safety PLC.

Now, on the other hand, a safety PLC is different in that it was purposely built, tested and certified to meet international safety requirements right off the shelf. A safety PLC is different from a conventional PLC in many ways, such as:

  • Redundancy of onboard devices which are continuously monitored by a watchdog circuit
  • Continuously monitors inputs with a smart circuit to detect failure or malfunction
  • Additional safety circuitry between the output switching device and an actual device, which will detect system failure and facilitate a safe shut down by reverting to a known state

Pros of using a safety PLC:

  • Major savings on field wiring (Safety Circuit Category 3-4)
  • Flexible
  • Scalable
  • Remote I/O capability with safety
  • Safety control and standard control in one unit
  • Good diagnostic capability
  • Perfect for multiple e-stop zone applications

Cons of using a safety PLC:

  • Upfront cost is higher
  • Requires programming
  • Possibly too complex for certain applications
  • Requires educated maintenance people

To summarize, safety relays with a normal PLC are not recommended for applications requiring 5+ relays or 2+ e-stop zones. A safety PLC can be very cost effective when packaged in one unit with its ability to increase production and its allowance for scalable solutions.  Carefully examine the pros and cons of each option when designing your controls system to get the best results on every project.

Vijay Kapila is the Controls Operations Manager at Bastian Solutions and has been with the company since 2008. He started with Bastian Solution as a Controls Software Engineer. He led multiple successful controls and software projects as a Controls Software Engineer before taking on the role as Controls Operations Manager. His expertise is distribution center automation and machine automation.

Tags: , , ,

6 comments

  1. Scott A. Somers says:

    Mr. Kapila,

    Thank you for this article, very informative and timely for me.

  2. loganathan.M says:

    good evening sir, i m a robotics and automation engineering student. i studied PLC and SCADA your article is very useful to me. and i m familiar with SIEMENS PLC SOFTWARE. If u read this comment please sir reply me….

  3. S K Bose says:

    An excellent article indeed on the pros and cons of Safety Automation systems. I wanted to know whether the normal process functions (apart from the safety functions) can be performed by these Safety PLCs. Also, whether the PLC makes like ABB, GE etc are into manufacuring Safety PLCs?

  4. Vijay Kapila says:

    A Safety PLC is able to perform all process functions which a normal PLC can. A safety PLC is a normal PLC with Safety built into it. Majority of manufacturers(including ABB and GE) have safety PLC’s in their offerings.

  5. Roberto Pregnolato says:

    Vijay, your article is very interesting and informative. I had the opportunity to program safety PLCs for some machines and the programming tools for the safety are really reliable and easy to understand.

Leave a Reply

Your email address will not be published.